CONTACT:

800-443-9228
972-466-1999
Fax
972-466-1878

sales@exactexchanger.com

PO Box 795187
Dallas, TX 75379-5187
Best Viewed
at
800 x 600


Google© Website Translator: SpanishFrenchItalianGermanPortuguese

AA Series

PERFORMANCE

Inlet
Temp.

Approach
Temp.

AFTERCOOLER MODEL

AA50

AA75

AA100

AA150

AA200

AA250

AA300

150

5

209

258

451

655

826

883

1064

10

451

546

584

1339

1491

1919

2090

15

527

546

584

1396

1491

2038

2090

20

527

546

584

1396

1491

2038

2090

200

5

141

196

323

474

574

611

743

10

273

374

570

1021

1458

1823

2042

15

428

533

570

1294

1458

1823

2042

20

515

533

570

1367

1458

1969

2042

250

5

114

153

267

376

455

468

591

10

206

284

455

656

797

876

1068

15

306

411

556

941

1160

1313

1541

20

416

521

556

1256

1432

1773

1988

300

5

93

130

227

320

388

392

497

10

168

231

388

544

657

716

868

15

244

333

535

767

935

1040

1247

20

324

438

544

1002

1222

1390

1626

350

5

81

114

203

228

341

349

438

10

142

199

335

471

569

609

755

15

207

280

532

658

796

869

1056

20

268

366

532

837

1027

1149

1365

400

5

71

102

180

254

301

302

392

10

125

172

294

419

502

529

658

15

176

243

396

572

698

752

917

20

231

314

509

725

886

980

1176

Note: Suction condition 70ºF & 60% relative humidity @ 14.7 PSIA. Maximum 2 PSI pressure drop at rated capacity.

Selection Procedure: Enter the chart on the left at the appropriate inlet temp. and approach temp. Move to the right until you reach a SCFM value  greater than or equal to the required capacity. Select the aftercooler model.


Copyright © 1999-2000 Exact Exchanger, Inc. All rights Reserved.
All information is correct at time of publication, but subject to change without notice.
Questions or comments about this site? Contact: